Legrand 310189 - KEOR single-phase UPS 1500VA

Price: €299,99 Including VAT / PC
Code LEG310189
Brand Legrand
EAN 3414971232068
   Product available!
Description

Legrand 310189 - KEOR single-phase UPS 1500VA

Legrand 310189: keor SP UPS 1500 VA / 900 W line interactive, 6 IEC outlets, USB. The Legrand 310189 is a Keor SP single-phase UPS rated 1500 VA / 900 W with line interactive VI technology. It has an electronic AVR stabilizer that protects the load against mains disturbances and sealed VRLA lead-acid batteries. It has 6 IEC output sockets, powered also during mains failure and protected against surges, and a USB socket to charge mobile devices. With the USB HID port and the free software you can monitor the UPS and safely shut down a PC running Windows or Linux.
Rated current6.9 ARated current6.6 ARated voltage230 VRated power1500 VASoldPer piece
Features and functions
›Single-phase line interactive VI UPS, 1500 VA / 900 W
›Built-in electronic AVR stabilizer
›6 IEC output sockets with backup and surge protection
›10 minutes backup time with a typical workstation (minimum 5 minutes at 80% load)
›USB type A port for charging mobile devices (5 V, 1 A)
›USB HID type B port and free monitoring and shutdown software for Windows and Linux
›Status LED bar and audible alarms
›Protection against overload, short circuit and deep battery discharge
Technical data
Technical data
Rated power1500 VA
Active power900 W
TechnologyLine interactive VI
Waveform in battery modePseudo-sinusoidal
Transfer time2...6 ms (typical)
EfficiencyUp to 98%
StabilizerElectronic AVR
Input
Rated voltage230 V
Voltage range170...280 V
Rated frequency50/60 Hz ± 5 Hz, automatic detection
Rated current6.9 A
Input cableDetachable 3x1 mm² with German/French standard plug
Output
Rated voltage (battery mode)230 V ± 10%
Rated frequency (battery mode)50/60 Hz ± 1 Hz, automatic detection
Rated current6.6 A
Output sockets6 IEC sockets
USB charging portType A female, 5 V, 1 A
Overload in mains modeShutdown after 5 min with load >100%, after 5 s with load >120%
Batteries
Battery typeSealed maintenance-free lead/acid (VRLA)
Batteries2 x 12 Vdc 9 Ah
Backup time10 min with a typical workstation; minimum 5 min at 80% load
Typical recharge time4...6 hours
Deep discharge protectionYes
Communication and indications
Interface2 buttons and 4-LED bar
Communication portUSB HID type B
SoftwareFree, monitoring and emergency shutdown for Windows and Linux
AlarmsVisual (LED) and audible (buzzer)
Ambient conditions
Operating temperature0...+40 °C
Relative humidity<95% non-condensing
Noise at 1 m<40 dB
Degree of protectionIP20
Dimensions and installation
Dimensions148 x 173 x 380 mm
Net weight9.6 kg
Standards and approvals
Reference standardsEN 62040-1/2/3
SafetyDirective 2014/35/EU, EN 62040-1
EMCDirective 2014/30/EU, EN 62040-2 (category C2)
MarkingCE
Identification
Legrand code310189
System / rangeKeor SP single-phase UPS
Data from Legrand product sheet and Legrand technical documentation.
Matching products
Other versions of the range
Learn more
Item code LEG310189Manufacturer code 310189EAN 3414971232068Sold per piece