Technical data
ABB code2CSR245073R1164
TypeDS201 L H C16 AC30
Product typeResidual current circuit breaker with overcurrent protection (RCBO)
Number of poles1P+N
Rated current (In)16 A
Tripping characteristicC
Residual current type / sensitivity (IΔn)Type AC / 30 mA
Short-circuit capacity Icn / Icu / Ics4.5 kA / 6 kA / 4.5 kA
Rated residual breaking capacity (IΔm)3000 A
Rated voltage Ue / test button voltage Ut230 V / 170...254 V
Insulation voltage Ui / impulse withstand voltage Uimp500 V AC / 4 kV
Rated frequency50 Hz
Energy limiting class / overvoltage category / pollution degree3 / III / 2
Electrical / mechanical life10000 / 20000 operations
Degree of protectionHousing IP4X, terminals IP2X
Operating / storage temperature-5...+55 °C / -40...+70 °C
TerminalsCage terminal with integrated fail-safe, 25 mm² top and bottom
Tightening torque2 Nm
MountingDIN rail EN 60715 (35 mm), any position
Modules / dimensions (H x D x W)2 / 85 x 69 x 35 mm
Weight182 g
Total power loss4.5 W
Neutral terminal positionRight
Reference standardsEN 61009-1, EN 61009-2-1