›Charging of 1 electric vehicle, single-phase 3.7 kW (16 A) or 4.6 kW (20 A)
›Upper Type 2 socket (T2S) for Mode 3 with locking system
›Lower 2P+E 16 A domestic socket for Mode 1/2
›Integrated 13.56 MHz RFID reader and RJ45 Ethernet communication kit
›EV CHARGE app via Bluetooth: status, daily scheduling, activation, power setting, software update
›3h/6h/9h delayed start and forced start from the pushbutton
›Inputs for ON/OFF and HP/HC (time slot) remote control, Modbus RS485 connection
›Integrated 6 mA DC fault current detection
›Wall or floor installation with pedestal 059052
›IP44 and IK08, indoor or outdoor use
Electrical data
Rated voltage230 V~ (phase + N)
Frequency50/60 Hz
Charging current16 A or 20 A (settable)
Power3.7 kW (16 A) / 4.6 kW (20 A)
Tolerated voltage195 - 265 V
Impulse voltage (Uimp)4 kV
Insulation voltage (Ui)230 V
Conditional short circuit4.5 kA / 6 kA / 10 kA depending on upstream protection
Admissible thermal limit in S/C16 000 A²s
Stand-by consumption8.6 W
Power dissipated when charging 16 A / 230 V17.4 W
DC fault current detection6 mA
Overload detection7.5 s at 125% In, 100 s at 115% In
Sockets and charging modes
Upper socketType 2 3P+N (single-phase compatible), IEC 62196-2, Mode 3 with lock
Lower socketType E/F domestic 2P+E 16A-250V, Mode 1/2, magnetic detection of Green'Up plug
Extension cordsUse forbidden
Connection and protection
Supply terminalsPhase/Neutral/Earth screw terminals from 2.5 to 10 mm²
Upstream residual current protection30 mA type A or F (or type F according to local rules)
16 A line (3.7 kW)Minimum cross-section 2.5 mm², RCBO GN8813F16
20 A line (4.6 kW)Minimum cross-section 4 mm², RCBO GN8813F20
Recommended shunt trip (KM1)F80ST1
Safety output signal12V= pulses for shunt trip item 4 062 76
Recommended earth resistanceNot above 30 Ω/N (N = charging points)
Earthing systemTNS, TT (IT with isolation transformer)
Communication
BluetoothBLE, 2400 - 2483.5 MHz, EV CHARGE app (iOS 7.0 and Android 4.4 or later)
EthernetRJ45 (Cat. 6 FTP/UTP cable), web management pages
RFID13.56 MHz (ISO14443A/B, ISO15693, NFC)
BusModbus RS485 (Belden 9842 cable)
Environment and protection
Protection ratingIP44 (IEC 60529), plugs inserted or not
Impact resistanceIK08 (EN 62262)
Operating temperature-25 °C / +40 °C (peak 50 °C)
Storage temperature-25 °C / +70 °C (peak 80 °C)
Relative humidity0 - 90% non-condensing
Noise level< 40 dBA at 1 m
InstallationIndoor or outdoor, restricted access area
Dimensions
Dimensions (H x W x D)365 x 295 x 140 mm
Weight4 kg
With pedestal 059052 (H x W x D)1200 x 295 x 135 mm, 18.5 kg
Standards
ProductIEC 61851-1, IEC 61851-22, IEC TS 61439-7 (AEVCS), NF EN 17186
Electrical safetyClass 1 IEC 61140
InstallationIEC 60364-7-722
Identification
Legrand code059005
System / rangeGreen'Up Premium
Data from Legrand catalogue product sheet and Legrand technical data sheets and instructions.