›Charging of 1 electric vehicle, single-phase 3.7 kW (16 A) or 4.6 kW (20 A)
›Metal housing, single-sided
›Type 2 socket (T2S) for Mode 3 with locking system
›German standard 2P+E 16 A socket for Mode 2, also for e-bikes and scooters
›EV CHARGE app via Bluetooth: status, daily scheduling, activation, power setting, software update
›12V= volt-free contact inputs for Hp/Hc enabling (deferrable) and On/Off (non-deferrable)
›Expandable with IP interface 059056 and RFID reader 059059
›Integrated 6 mA DC fault current detection
›IP55 and IK10, indoor or outdoor use
›Wall (059060) or floor (059062) installation
Electrical data
Rated voltage230 V~ (phase + N)
Frequency50/60 Hz
Charging current16 A or 20 A
Power3.7 kW (16 A) / 4.6 kW (20 A)
Tolerated voltage195 - 265 V
Impulse voltage (Uimp)4 kV
Insulation voltage (Ui)230 V
Conditional short circuit4.5 kA / 6 kA / 10 kA depending on upstream protection
Admissible thermal limit in S/C16 000 A²s
Stand-by consumption8.9 W
DC fault current detection6 mA
Overload detection8 s at 125% In
Sockets and charging modes
Upper socketType 2 3P+N (single-phase compatible), IEC 62196-2, Mode 3 with lock
Lower socketType E/F domestic 2P+E 16A-250V, Mode 2, magnetic detection of Green'Up plug
Extension cords and adaptersUse forbidden
Connection and protection
Supply terminalsPhase/Neutral/Earth screw terminals from 2.5 to 10 mm², rigid H07 V R/U or flexible H07 V K with ferrule
Upstream residual current protection30 mA (Idn 0.03 A) type A or F
RCBO (Q1)GN8813F16 (16 A) / GN8813F20 (20 A)
Shunt trip (KM1)F80ST1
Safety output command12V= pulses for shunt trip item 4 062 76
Earth resistanceMaximum 30 Ω/N (N = charging points)
Earthing systemTNS, TT (IT with isolation transformer)
Communication
BluetoothBLE, 2400 - 2483.5 MHz, EV CHARGE app (iOS 7.0 and Android 4.4 or later)
IP interface (accessory 059056)RJ45 or 2.4 GHz Wi-Fi, web pages, Modbus RS485
RFID (accessory 059059)13.553 - 13.567 MHz
Environment and protection
Protection ratingIP55 (IEC 60529), plugs inserted or not
Impact resistanceIK10 (EN 62262)
Operating temperature-25 °C / +40 °C (peak 50 °C)
Storage temperature-25 °C / +70 °C (peak 80 °C)
Relative humidity0 - 90% non-condensing
Corrosivity class3C2 and 4C2 according to IEC 60721-3-3
Noise level< 40 dBA at 1 m
InstallationIndoor or outdoor, restricted access area
Dimensions
Height365 mm
Width140 mm
Depth295 mm
Standards
ProductIEC 61851-1, IEC 61851-22, IEC TS 61439-7 (AEVCS), NF EN 17186
Electrical safetyClass 1 IEC 61140
InstallationIEC 60364-7-722
Radio directive2014/53/EU
Identification
Legrand code058041
System / rangeGreen'Up Premium
Data from Legrand catalogue product sheet and Legrand technical data sheets and instructions.