Technical
Dielectric Test Voltage50 / 60 Hz - 1 min 2 kV
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(125 V DC) 10 kA / (230 V AC) 20 kA / (400 V AC) 10 kA / (440 V AC) 10 kA / (48 V DC) 20 kA / (230 V) 20 kA / (400 V) 10 kA
Rated Service Short-Circuit Breaking Capacity (Ics)(230 V AC) 15 kA / (400 V AC) 7.5 kA / (440 V AC) 7.5 kA
Power Supply ConnectionArbitrary
Contact Position IndicationRed ON / Green OFF
Energy Limiting Class3
Electrical Endurance20000 AC cycle
Mechanical Endurance20000 cycle
Number of Protected Poles2
Number of Poles2P
Tightening Torque2.8 N·m
Actuator MarkingI / O
Connecting CapacityBusbar 10/10 mm² / Flexible with Ferrule 0.75 ... 25 mm² / Flexible 0.75 ... 25 mm² / Rigid 0.75 ... 35 mm² / Rigid 0.75 ... 35 mm² / Stranded 0.75 ... 35 mm²
Installation Sizeacc. to DIN 43880 1
Wire Stripping Length12.5 mm
Electrical
Tripping CharacteristicC
Rated Operational Voltageacc. to IEC 60898-1 400 V AC / acc. to IEC 60947-2 440 V AC
Operational VoltageMaximum (Incl. Tolerance) 125 V DC / Maximum (Incl. Tolerance) 440 V AC / Minimum 12 V AC / Minimum 12 V DC
Rated Insulation Voltage (Ui)acc. to IEC/EN 60664-1 440 V
Input Voltage TypeAC/DC
Rated Current (In)25 A
Rated Short-Circuit Capacity(AC) 6 kA / (DC) 6 kA
Frequency (f)50 Hz
Rated Frequency (f)50 / 60 Hz
Power Loss6.4 W / at Rated Operating Conditions per Pole 3.2 W
Overvoltage CategoryIII
Design
Housing MaterialInsulation Group II, RAL 7035
Dimensions
Width in Number of Modular Spacings2
Product Net Width35 mm
Product Net Height88 mm
Product Net Depth / Length69 mm
Product Net Weight0.23 kg
Pole Net Weight0.125 kg
Built-In Depth (t2)69 mm
Dimension Diagram2CDC022007F0010
Installation
Mounting TypeDIN-Rail
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 / TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting Positionany
Identification
ABB typeS202-C25
ABB product ID2CDS252001R0254
Order codeS466103
EAN4016779466103
Data from the ABB product page (new.abb.com).