Specialcavi Baldassari SO40001ZROM100 - CPR Solar Cable for Photovoltaics H1Z2Z2-K 4mm2 RED
Price: €1,00 Including VAT / LM
Code: BALSO40001ZROM100
Brand: Specialcavi Baldassari
EAN: 0000000727136
DESCRIPTION
Specialcavi Baldassari SO40001ZROM100 - CPR Solar Cable for Photovoltaic H1Z2Z2-K 4mm2 RED
Outer diameter: 5.5 mm
H1Z2Z2-K
Construction characteristics
Core: Flexible tinned copper, class 5
Insulation: LSZH compound based on cross-linked rubber
Outer sheath: LSZH compound based on special cross-linked rubber, UV-resistant
Colours: Red (based on RAL 3000)
Electrical characteristics
Core operating voltage:
Rated operating voltage:
1.0kV AC - 1.5kV DC (also grounded)
Maximum operating voltage:
1.2kV AC - 1.8kV DC. (also grounded)
Sheathing operating voltage:
Rated operating voltage:
1.0kV A.C. - 1.5kV D.C. (also grounded)
Maximum operating voltage:
1.2kV A.C. - 1.8kV D.C. (also to earth)
Test voltage: 15kV C.C
Normative reference
EN 50618
EN 60228 EN 50395
EN 50618 EN 50395 EN 62230
EN 50618 EN 50396 EN 60228
EN 60811-401 EN 50618
EN 60811-504 EN 60811-505 EN 60811-506 EN 50618
EN 60811-403 EN 50396 EN 50618
EN 60811-403 EN 50396 EN 50618
EN 50618br /> EN 50618 EN 50289-4-17 method A
EN 60068-2-78
EN 60811-503
EN 60332-1-2
EN 61034-2 (LT≥60%)
EN 50525-1
EN 50618 EN 60216-1 EN 60216-2
FIRE REACTION CLASS
EN 50575:2016 Dca- s2, d2, a1
Temperatures
Minimum operating temperature: -40°C
Maximum operating temperature: +90°C
Maximum short circuit temperature: +250°C
Applications
Cable complying with the requirements of the Construction Products Regulation (CPR EU 305/11), with the aim of limiting the production and spread of fire and smoke.Single-core halogen-free cable suitable for connecting the various elements of photovoltaic and solar systems. The H1Z2-K cable has excellent UV and weather resistance. The service life of the cable is estimated to be approximately 25 years (EN 50618) and the expected period of use at a maximum conductor temperature of 120°C and a maximum ambient temperature of 90°C is limited to 20,000 hours. For fixed installation outside and inside buildings, without protection or inside exposed or embedded pipes
Suitable for applications not covered by the CPR regulation and for installation inside an enclosed environment, except in cases with specific risks of fire ignition/propagation where the use of cables with higher fire reaction performance is recommended (at least Cca-s3,d1,a3). Presence of water: condition AD7.