Electric Cable FS17-1VL - CPR FS17 Violet Cable 1mm2

Price: €0,24 Including VAT / MT
Code CONFS17-1VL
Brand Electrical Cable Made in Italy
EAN 8013086967527
Description

Electric Cable FS17-1VL - CPR FS17 Violet Cable 1mm2

FS17 450/750 V single-core cable with a flexible copper conductor and S17 grade PVC insulation. It is the building wire that replaced the old N07V-K in Italian residential and commercial installations: it is laid inside conduits and trunking, also in bundles, and complies with the Construction Products Regulation (CPR) in class Cca-s3,d1,a3. Cross-section 1 mm², colour violet.
Formation1 mm²Outer diameter2.7-3 mmVoltage450/750 VMax temp.70 °CCPR classCca-s3,d1,a3SoldPer metre, minimum 200 m
Choose the variant
Same cross-section, other colours
Other cross-sections in violet
1 mm²1.5 mm²
Where it can be installed
Indoor, in conduit or trunking
Bundled installationclass Cca
Outdooronly protected in conduit
Buried
Mobile use
›Residential and commercial wiring: lighting, socket circuits and risers inside conduits, trunking and ducts
›Bundled installation in buildings with fire safety requirements (schools, offices, buildings over 24 m) thanks to class Cca-s3,d1,a3
›Wiring of switchboards and lighting and control equipment
›Not suitable for burial or outdoor use without protection: use a sheathed cable such as FG16R16
Outer diameter and cross-sectionsource: Baldassari Cavi, Pecso and La Triveneta Cavi catalogues
outer Ø 2.7-3 mmCross-section 1 mm²copper Ø 1.3 mm
Estimated outer diameter
2.7 - 3 mm
typical 2.7 mmmaximum 3 mm
The low value is the typical production value, the high one the maximum declared by manufacturers. The cable you receive falls within this range, which varies slightly between brands and batches.
Cross-section and diameter are not the same thing. The cross-section (1 mm²) is the copper area of each conductor and determines how much current the cable can carry: the copper of a 1 mm² conductor is about 1.3 mm in diameter. The outer diameter is the total thickness with insulation and sheath: you need it to choose conduits, trunking and cable glands.
Technical data
Electrical data
Formation1x1
Rated voltage Uo/U450/750 V
Max conductor resistance at 20 °C19.5 ohm/km
Approx. current rating
In conduit or trunking in air at 30 °C12 A
Construction
Conductorflexible annealed copper, class 5 (IEC 60228)
InsulationS17 grade PVC, no sheath
Colourviolet
Approx. weight14-16 kg/km
Temperatures
Max operating temperature70 °C
Min installation temperature5 °C
Short-circuit temperature160 °C
Installation
Min bending radius4 times the outer diameter
Max pulling stress50 N/mm²
Fire and standards
CPR fire reaction classCca-s3,d1,a3 (EN 50575)
StandardsCEI UNEL 35716, CEI 20-40, EN 50575
Approximate current ratings from the Baldassari Cavi and La Triveneta Cavi catalogues. The real value depends on installation, nearby circuits and temperature: for sizing refer to IEC 60364 / CEI 64-8 and the CEI UNEL 35024 tables.
The code explained
?How to read the code FS17 1x1Tap to open the letter by letter explanation
FS171x1
  • Fflexible stranded conductor (class 5)
  • S17S17 grade PVC insulation with improved CPR fire performance
  • (no sheath letter) single-core cable without sheath: always protect it in conduit or trunking
  • 1x1conductor cross-section in mm², that is the copper area (not the diameter)
In our item code (CONFS17-1VL) the first 3 letters identify the brand, or CON for generic cables; the rest repeats the manufacturer code or the cable designation with its formation.
Recommended accessorieschosen for the cross-section and the outer diameter
Terminals and cable lugs
Terminal blocks
Crimping tools
Related categories
Item code CONFS17-1VLEAN 8013086967527Sold per metre, minimum 200 m