FREE CUTTINGcut to the exact length you order
Electric Cable FS18OR18-7G1.5 - Brown Cable FS18OR18 Section 7G1.5
FS18OR18 300/500 V multi-core cable with S18 grade PVC insulated cores and R18 grade PVC sheath. It is the CPR version (Cca-s3,d1,a3) of the old FROR: used for control, signalling and small power supplies inside buildings. Formation 7G1.5: 7 cores of 1.5 mm², one yellow-green for earthing.Formation7G1.5Outer diameter8.7-10.1 mmVoltage300/500 VMax temp.70 °CCPR classCca-s3,d1,a3SoldPer metre
Choose the variant
All available formations
7G1.5
Where it can be installed
Bundled installationclass Cca With 450/750 V cablesseparate conduits ›Control and signalling circuits, automation, switchboards and machines
›Supply of appliances and small loads in dry or wet indoor locations
›Installation in free air, conduit, trunking and metal structures; temporary outdoor use allowed
›Not for burial and not in the same conduits as 450/750 V or 0.6/1 kV cables (lower insulation voltage)
Outer diameter and cross-sectionsource: Baldassari Cavi, Pecso and La Triveneta Cavi catalogues
Estimated outer diameter
8.7 - 10.1 mm
typical 8.7 mmmaximum 10.1 mm
The low value is the typical production value, the high one the maximum declared by manufacturers. The cable you receive falls within this range, which varies slightly between brands and batches.
Cross-section and diameter are not the same thing. The cross-section (1.5 mm²) is the copper area of each conductor and determines how much current the cable can carry: the copper of a 1.5 mm² conductor is about 1.5 mm in diameter. The outer diameter is the total thickness with insulation and sheath: you need it to choose conduits, trunking and cable glands.
Technical data
Electrical data
Formation7G1.5
Rated voltage Uo/U300/500 V
Max conductor resistance at 20 °C13.3 ohm/km
Approx. current rating
In conduit or trunking in air at 30 °C13 A
Construction
Conductorflexible annealed copper, class 5
InsulationS18 grade PVC
SheathR18 grade PVC
Approx. weight168-169 kg/km
Temperatures
Max operating temperature70 °C
Min installation temperature0 °C
Short-circuit temperature160 °C
Installation
Min bending radius4 times the outer diameter
Fire and standards
CPR fire reaction classCca-s3,d1,a3 (EN 50575)
StandardsCEI UNEL 35720, CEI 20-40/2-1, EN 50575
Approximate current ratings from the Baldassari Cavi and La Triveneta Cavi catalogues. The real value depends on installation, nearby circuits and temperature: for sizing refer to IEC 60364 / CEI 64-8 and the CEI UNEL 35024 tables.
The code explained
?How to read the code FS18OR18 7G1.5Tap to open the letter by letter explanation
FS18OR187G1.5
- Fflexible stranded conductor (class 5)
- S18S18 grade PVC insulation
- Oseveral cores laid up in a round cable
- R18R18 grade PVC sheath, CPR rated
- 7G1.57 cores (conductors); G means one of the cores is yellow-green for earthing; 1.5 mm² is the cross-section of each conductor, that is the copper area, not the diameter
In our item code (CONFS18OR18-7G1.5) the first 3 letters identify the brand, or CON for generic cables; the rest repeats the manufacturer code or the cable designation with its formation.
Recommended accessorieschosen for the cross-section and the outer diameter
Terminals and cable lugs
Terminal blocks
Crimping tools
Cable glands for Ø 8.7-10.1 mm
Related categories
Item code CONFS18OR18-7G1.5EAN 8013086168245Sold per metre