Specialcavi Baldassari FNZ10007G - CPR Cable FROR16 7G1.00mm²
Outer diameter: 8.1 mm
FROR16
Constructional Characteristics
Core: Flexible red copper conductor, class 5
Insulation: PVC-based compound, R2 quality
Cord: Twisted/corded cores with concentric crowns
Outer jacket: PVC-based compound, R16 quality
Colours: Grey (based on RAL 7035)
Electrical characteristics
Core operating voltage
- 300/500V cross section ≤ 0.75 mm²
- 450/750V section ≥ 1.00 mm²
Sheathing operating voltage: 450/750V
Test voltage
- 2000V section ≤ 0.75 mm²
- 2500V cross section ≥ 1.00 mm²
Normative reference
CEI 20-29 IEC 60228
CEI 20-11 EN 50363
CEI 20-22 II
CEI EN 60332-3-24 Cat.C IEC 60332-3-24 Cat.C
CEI UNEL 36762
FIRE REACTION CLASS
EN 50575:2016 Cca - s3, d0, a3
Temperatures
Minimum operating temperature: -15°C
Maximum operating temperature: +70°C
Maximum short-circuit temperature: +160°C
Applications
Cable complying with the requirements of the Construction Products Regulation (CPR EU 305/11), with the aim of limiting the production and spread of fire and smoke.
Multi-core cable for control, signalling, command and measurement installations. The non-fire propagation characteristics and small external dimensions make it particularly suitable for intercom and switchboard applications.
This cable can always be installed in coexistence with 450/750V energy cables, and furthermore, if used to supply category 0 systems (rated voltage less than or equal to 50V, if alternating current, or 120V, if direct current or not corrugated), it can also be installed in coexistence with 0.6/1kV energy cables supplying loads with a rated voltage of 230/400V. This does not exclude possible problems due to electromagnetic interference.
Underground installation, even if protected, is not permitted.